Field Setting
SiUS39-602
86
Test Operation
3.1.7
Centralized Control Group No. Setting
BRC1C Type
If carrying out centralized control by central remote controller or unified ON/OFF
controller, group No. must be set for each group individually by remote controller.
Group No. setting by remote controller for centralized control
1. When in the normal mode, push the
button for 4 seconds or more, and operation
then enters the “field setting mode.”
2. Set mode No. “00” with the
button.
∗
3. Push the
button to inspect the group No. display.
4. Set the group No. for each group with the
button (The group No. increases in the
manner of 1-00, 1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF controller
displays only the group No. within the range selected by the switch for setting each address.)
5. Push the timer
button to define the selected group No.
6. Push the
button to return to the normal mode.
Even if not using a remote controller, connect the remote controller when setting the group
No., set the group No. for centralized control, and disconnect after making the setting.
Set the group No. after turning on the power supply for the central remote controller, unified
ON/OFF controller, and indoor unit.
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...