Troubleshooting by Indication on the Remote Controller
SiUS39-602
152
Troubleshooting
2.21
“
F6
”
Refrigerant Overcharged
Remote
Controller
Display
F6
Applicable
Models
REYQ72M, 96M
Method of
Malfunction
Detection
Refrigerant overcharge is detected from the receiver gas pipe temperature during test
operation.
Malfunction
Decision
Conditions
When the receiver gas pipe temperature is lower than evaporating temperature during test
operation.
Supposed
Causes
Refrigerant overcharge
Disconnection of the receiver gas pipe thermistor
Troubleshooting
(V2797)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
receiver gas pipe
temperature thermistor
installed the gas relief
pipe on top of
receiver?
Is the
characteristic of the
receiver gas pipe
thermistor
normal?
Refrigerant overcharged.
YES
NO
NO
Replace thermistor.
Install thermistor correctly.
YES
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...