Control Specification
SiMT041311E
47
Function and Control
2.2.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(The function is not activated when defrosting.)
2.2.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
A
(Hz)
52
B
(Hz)
68
C
(Hz)
80
D
(Hz)
98
E
(seconds)
120
F
(seconds)
120
G
(seconds)
480
H
(seconds)
60
(sec.)
Time
(R13906)
(Hz)
Frequency
C
D
B
E
F
G
H
A