Troubleshooting
SiMT041311E
173
Service Diagnosis
2.36 Outdoor Unit PCB Abnormality or Communication
Circuit Abnormality
Error Code
U4
Method of Error
Detection
Detection within the programme of the microcomputer
Error Decision
Conditions
The programme of the microcomputer does not work in order.
Indoor-outdoor unit signal transmission cannot be performed for more than 15 seconds.
Supposed
Causes
Power supply voltage is not as specified.
Improper earth work
Defective varistor or fuse on the outdoor unit PCB
Defective thermal fuse on the terminal board of the outdoor unit
Disconnection of connecting wires
Defective outdoor unit PCB
Noise
Disturbed power supply waveform
Wrong wiring
Improper insulation of the connecting wires and earth
Defective indoor unit PCB