SiMT041311E
Troubleshooting
Service Diagnosis
180
2.41 Lights-out of Microcomputer Status Lamp
Error Code
No display
Method of Error
Detection
When a microcomputer fault is detected, LED A turns off.
Error Decision
Conditions
Supposed
Causes
Outdoor unit PCB is not power supplied.
Power supply failure due to noise
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R19691)
∗
Before you check the LED A,
cancel the standby electricity
saving function by starting fan
operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.
Is correct power supplied?
Is LED A turned off?
YES
Blink
OFF or Blink
YES
Does the LED A blink?
OFF or ON
Is voltage of 5 V
applied b5V
and GND ?
Restart operation.
NO
ON
NO
Turn on the power.
Turn on the breaker.
*Do not work on or touch
components other than
specified part. (Doing so
may cause a short circuit.)
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Remove noises (from the
power supply).
Replace the outdoor unit
PCB.