SiMT041311E
Main Functions
Function and Control
16
Detail
COOLING, DRY COOLING
•
When the up/down airflow direction is set to
Circulation
, circulation airflow starts.
•
When the up/down airflow direction is set to
AUTO
, operation starts in circulation airflow,
then switches to BREEZE airflow when the room temperature becomes stable.
•
Once it switches to BREEZE airflow, it does not switch back to circulation airflow.
•
When you want to switch back to circulation airflow, set the up/down airflow direction to
AUTO
again.
•
Circulation airflow switches to BREEZE airflow when the conditions below continue for 10
minutes.
(1) Thermostat off
OR
(2) Temperature difference is in the range of zone E or lower.
SARARA DRY
•
When the up/down airflow direction is set to
Circulation
, circulation airflow starts.
•
When the up/down airflow direction is set to
AUTO
, operation starts in circulation airflow,
then switches to BREEZE airflow when the room temperature becomes stable.
3.0
2.5
2.0
1.5
1.0
0.5
0
–0.5
–1.0
–1.5
–2.0
A
B
C
D
E
F
G
H
I
J
*Decreases when the operation starts
Zone
Decreasing
Increasing
A
B
C
D
E
F
G
H
I
J
Room thermistor temperature – Target temperature (˚C)
High
Low
Room
temperature
(R19695)
28˚C
26.5˚C
BREEZE
airflow
Circulation
airflow
(R20201)