SiMT041311E
Main Functions
Function and Control
30
1.8
AUTO Operation
Operation
∗
Refer to the operation manual for details.
Outline
Automatic Cooling / Heating Function
When the AUTO operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C).
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value
.
C = 0°C
3. Thermostat ON/OFF point and operation mode switching point are as follows.
Tr means the room thermistor temperature.
(1) Heating
→
Cooling switching point:
Tr
≥
Tt + 2.5°C
(2) Cooling
→
Heating switching point:
Tr < Tt – 2.5°C
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr
≥
Ts: Cooling operation
Tr < Ts: Heating operation
Ex: When the target temperature is 25°C
Cooling
→
23.0°C: Thermostat OFF
→
22.0°C: Switch to heating
Heating
→
26.5°C: Thermostat OFF
→
27.5°C: Switch to cooling
(R19702)
AUTO
(R11893)
Target tempe 2.5˚C
Heating Operation
Target temperature – 2.5˚C
Cooling Operation
Target tempe 1.5˚C
= Thermostat OFF
Target temperature – 2.0˚C
= Thermostat OFF