ESIE13-02
Troubleshooting
61
Part 4 – Troubleshooting
4
3
4
5
4
1.2.4
After Unit Shuts Down, It cannot be Restarted for a While
Applicable model
ERHQ011~016*
ERLQ004~016*
Error detection
method
Error generating
condition
Supposed causes
Overcurrent relay (for compressor)
Compressor protection thermostat
Overcurrent relay may act due to the following reasons:
Lower voltage of power supply
Excess level of high pressure
Insufficient size of power cable
Malfunction of compressor
Compressor protection thermostat may act due to the following reasons:
Internal leakage of four-way valve (There is no difference between suction and discharge
temperature)
Insufficient compression of compressor
Incorrect refrigerant
Faulty expansion valve
Insufficient circulation of refrigerant