ESIE13-02
Troubleshooting
69
Part 4 – Troubleshooting
4
3
4
5
4
1.2.10 The Water Pressure Relief Valve Opens
Applicable models
EHB*CA, EHV*CA
Error detection
method
Error generating
condition
Supposed causes -
corrective action
Possible causes
Corrective action
The expansion vessel is broken.
Replace the expansion vessel.
The water volume in the installation is too high.
Make sure that the water volume in the installa-
tion is under the maximum allowed value (refer
to the “Specifications” in databook).