Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
120
3
1
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Wait for 10 minutes after
the unit stops operating,
then check the following.
Connect correctly.
Replace the lead wire.
* Replace the outdoor unit PC board
(A1P) ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC board (A2P )
ERHQ***W1* / ERLQ***W1*
Is
there continuity in
each protection
HPS?
NO
Is
protection
HPS connector (*1)
correctly connected to
outdoor unit PC
board?
NO
YES
YES
YES
Is there
continuity in lead
wire?
NO
*1 Connector symbol
ERLQ011~016*V3 / ERHQ011~016*V3: X32A (A1P)
ERLQ011~016*W1 / ERHQ011~016*W1: X32A (A2P)