Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
104
3
1
4
5
4.2
“E3”
Abnormal High Pressure (Detected by the HPS)
Remote controller
display
E3
Method of
malfunction
detection
The protection device circuit checks continuity in the high pressure switch.
Malfunction
decision conditions
When the high pressure switch is actuated
Actuating pressure:
Supposed causes
Faulty high pressure switch
Disconnection in high pressure switch harness
Faulty connection of high pressure switch connector
Clogged hydro-box suction filter (in heating operation)
Dirty outdoor unit heat exchanger
Faulty outdoor unit fan
Refrigerant overcharge
Stop valve is left in closed
HPS settings
The table below contains the preset HPS values.
High pressure switch
Fuse
Open
Close
4.0 MPa +0/-0.15
3.0 +/-0.15
6.3A/250V