ESIE13-02
Additional Checks for Troubleshooting
163
Part 4 – Troubleshooting
4
3
4
5
4
6.13
Check No.15 - Check for Factors Causing Wet Operation
Note
Reference values for superheat degree to be used in the judgement of wet operation:
1
Suction pipe superheat degree: 4°C or more
2
Discharge pipe superheat degree: 5°C or less
(The values above must be used only for reference purposes. Even it is operated within the range
above, operation may be normal in other conditions)