Additional Checks for Troubleshooting
ESIE13-02
Part 4 – Troubleshooting
150
3
1
4
5
6
Additional Checks for Troubleshooting
6.1
Check No.1 - Outdoor Unit: Checking the Installation Condition
Check No.01
1
To check the installation condition, proceed as follows:
.
Change the
installation location.
No
Clean the heat
exchanger.
No
Change the
installation location
or direction.
No
Yes
Yes
Check the spaces for all air
passage around the suction
and discharge areas.
Check the outdoor ambient
temperature R1T.
This temperature must be
lower than 43°C.
Change the
installation location.
Yes
Does the
discharged air from
other outdoor units cause an
increase of the suction
temperature?
Is the
minimum space respected?
Is the
heat exchanger
clean?
Yes
Is there enough
air flow?
No