Error Codes: System Malfunctions
ESIE13-02
Part 4 – Troubleshooting
148
3
1
4
5
5.6
“U5”
Malfunction of Transmission between Hydro-box and Remote Controller
Remote controller
display
U5
Error generation
The error is generated when the microprocessor detects that the transmission between the hydro-box
and the remote controller is not normal over a certain amount of time.
Supposed causes
The possible causes are:
Malfunctioning remote controller
Malfunctioning indoor PCB
Outside cause (noise...)
Connection of two master remote controllers (when using two remote controllers).
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
All
indoor unit PCB
microcomputer normal
monitors
flashing
Is "U5"
displayed
constantly?
Resets
normally when
power supply is turned
off temporarily.
Malfunction could be
produced by noise.
Check the surrounding
area and restart operation.
Failure of remote controller
PC board or replacement
of defective indoor unit PC
board.
Problem could be caused
by external factor (noise
etc.) other than
malfunction.
Indoor unit PC board
replacement.
YES
YES
YES
NO
NO
NO