Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
110
3
1
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
YES
NO
NO
YES
Is the
UVW wiring
normal?
NO
YES
Is the
stop valve
open?
YES
NO
NO
Is
high pressure
higher than 2.6 MPa at
starting?
YES
NO
Check
and see whether
compressor is short-circuited
or ground.
YES
Are
inverter output
voltages the same for
3 phases?
Does low
or high pressure
vary even instantaneously
when restarting
compressor?
Check the installation
conditions.
Open the stop valve.
Connect correctly.
Remedy the cause.
Replace the compressor.
Replace the inverter PC board (A1P) ERHQ***V3* / ERLQ***V3*
(A2P) ERHQ***W1* / ERLQ***W1*
Replace the compressor.