Troubleshooting
ESIE13-02
Part 4 – Troubleshooting
70
3
1
4
5
1.2.11 The Water Pressure Relief Valve Leaks
Applicable models
EHB*CA, EHV*CA
Error detection
method
Error generating
condition
Supposed causes -
corrective action
Possible causes
Corrective action
Dirt is blocking the water pressure relief valve
outlet.
Check for correct operation of the pressure relief
valve by turning the red knob on the valve coun-
ter clockwise:
If you do not hear a clacking sound, contact
your local Daikin dealer.
In case the water keeps running out of the
unit, close both the water inlet and outlet
shut-off valves first and then contact your
local Daikin dealer.