Introduction
ESIE13-02
12
3
1
4
5
1.4.4
Brine
If applicable. See the installation manual or installer reference guide of your application for more
information.
1.4.5
Water
Avoid damages caused by deposits and corrosion. To prevent corrosion products and deposits,
observe the applicable regulations of technology.
Measures for desalination, softening or hardness stabilization are necessary if the filling and top-up
water have a high total hardness (>3 mmol/l-sum of the calcium and magnesium concentrations,
calculated as calcium carbonate).
Using filling water and top-up water which does NOT meet the stated quality requirements can cause
a considerably reduced service life of the equipment. The responsibility for this is entirely that of the
user.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area
immediately and contact your local dealer.
NOTICE
Make sure water quality complies with EU directive 98/83 EC.