ESIE13-02
Error Codes: System Malfunctions
145
Part 4 – Troubleshooting
4
3
4
5
4
(*) See also "Check No.10 - Outdoor Unit: Fan Speed Pulse" on page 159.
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
NO
YES
YES
Replace the outdoor fan
motor.
Replace the fuse.
Use only specified fuses.
* Replace the outdoor PC board
(A1P) ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC board
(A2P) ERHQ***W1* / ERLQ***W1*
Replace the outdoor PC
board (A1P) ERHQ***V3* / ERLQ***V3*
Replace the indoor PC
board.
There is no problem with
the unit. An external factor
(noise, etc.) other than unit
failure may be the cause.
Is the
resistance value of the
outdoor fan motor
normal
NO
YES
YES
YES
NO
Does the
fuse have continuity?
(*)
Is the
output voltage
normal?
NO
YES
Does "U4"
malfunction
reoccur?
NO
YES
Does
malfunction "U4" or "UF"
reoccur?
Check the resistance value of
the outdoor fan motor.
Check the fan output voltage. (*)
After turning OFF the power
supply, correctly insert the
connector of the fan motor and
then restore the power.
After turning OFF the power
supply, correctly insert the
connector of the fan motor and
then restore the power.
A
B
ERLQ***V3* / ERHQ***V3*
F6U
(*) FUSE Conductive
ERLQ***W1* / ERHQ***W1*
F7U