ESIE13-02
Error Codes: Outdoor Units
113
Part 4 – Troubleshooting
4
3
4
5
4
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
(*1): FUSE CONDUCTIVE
NO
YES
Replace the fan motor.
There is no problem with
the unit. An external
factor (noise, etc.) other
than unit failure may be a
cause of the malfunction.
Properly plug the fan motor
connector and then turn ON
the power again.
Is the
fan motor normal?
NO
YES
Is the fuse
conductive?
(*1)
YES
NO
Replace the fuse.
* Replace the outdoor PC
board (A1P) ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC
board (A2P) ERHQ***W1* / ERLQ***W1*
Does "E7"
appear again?
A
ERHQ011~016*V3
ERLQ011~016*V3
F6U (A1P) [outdoor pc board]
ERHQ011~016*W1
ERLQ011~016*W1
F7U (A2P) [inverter pc board]