Appendix A
57
In the following example, the local Major alarm indication is presented whenever any of the "checked" events
occur. Fiber link down or remote power failure will be reported as Major alarms.
Like wise, Minor alarms can also be assigned by events. This example shows the local Minor alarms are
reported only if UTP links are down.
In setting of the local and remote units, Major and Minor alarms are key when network management via SNMP
is used. When enabled here and when SNMP trap receivers are configured, Major and Minor alarm conditions will
be reported through the SNMP trap mechanism.
*********************************************
*** CTC UNION TECHNOLOGIES CO., LTD. ***
*** FRM220-1000EAS Ver:3.240 ***
*********************************************
<< Major Local Alarm Settings >>
<1> :[*]Fiber 1 Link Down
<2> :[*]Fiber 2 Link Down
<3> :[ ]UTP 3 Link Down
<4> :[ ]UTP 4 Link Down
<5> :[*]Remote A Power OFF
<6> :[*]Remote B Power OFF
<ESC>:Go to Previous Menu.
*********************************************
*** CTC UNION TECHNOLOGIES CO., LTD. ***
*** FRM220-1000EAS Ver:3.240 ***
*********************************************
<< Minor Local Alarm Settings >>
<1> :[ ]Fiber 1 Link Down
<2> :[ ]Fiber 2 Link Down
<3> :[*]UTP 3 Link Down
<4> :[*]UTP 4 Link Down
<5> :[ ]Remote A Power OFF
<6> :[ ]Remote B Power OFF
<ESC>:Go to Previous Menu.