81
can improve the system damping and eliminate oscillations through adjusting F4.12
F4.13.Generally do not need to adjust.
Code
Name
Setting Range
F4.14
Voltage separation control
0
~
6
【
0
】
F4.15
Keypad setting voltage
0~440V
【
0V
】
When separating V/F operates
,
the output voltage will set by the user.If F4.14 set to
1(keyboard set),setting the size of the output voltage instruction by F4.15,no more than
motor rated voltage and output voltage of bus bar can provide|(The maximum output
voltage of the bus can provide is
/
2
bus
V
).Voltage command also set by the way,such
as Analog value, input pulse, communication.100% is Corresponding to the motor rated
voltage value.
Code
Name
Setting Range
F4.16
Voltage rising time
0.1
~
3600.0S
【
1.0S
】
F4.17
Voltage falling time
0.1
~
3600.0S
【
1.0S
】
Separating V/F output voltage generated by the voltage instruction through the up
(down) slope.F4.16 set the up and speed of the slope,F4.17 set the down and speed of
the slope.Voltage rising (falling) time is equal to the output voltage from 0 up (down) to the
time required to 100.0%.
6.6 F5 Group: Input terminals
Code
Name
Setting Range
F5.00
Terminal control mode
0
~
3
【
0
】
This parameter defines four different control modes that control the inverter operation
through external terminals.