76
The torque is set using the high speed pulse HDI. 0 to F5.23 correspond to 0 to
F3.10.
6: Multi-speed setting torque
Set the torque using multi-speed. 100% corresponds to 0 to F3.10.
7: Communication set torque
Use communication to set the torque. Via MODBUS.
Code
Name
Setting Range
F3.12
Keyboard setting torque
0.0%
~
200.0%
【
50.0%
】
When F3.11 is set to 0, the torque is set by this parameter.
Code
Name
Setting Range
F3.13
Low speed torque boost during torque
control
0.0%
~
20.0%
【
5.0%
】
This parameter is the low speed torque boost value for torque control.
Code
Name
Setting Range
F3.14
Overvoltage PID proportional gain (Kp)
0.01
~
10.00
【
0.20
】
F3.15
Overvoltage PID integration time
0.00
~
100.00S
【
0.10S
】
The above two parameters are used for occasions where the bus voltage fluctuates
greatly, suppressing the rapid rise of the bus voltage and reducing the overvoltage alarm.
Code
Name
Setting Range
F3.16
VC controls the weak magnetic
coefficient
20.0
~
300.0%
【
100.0%
】
F3.17
VF control weak magnetic coefficient
20.0
~
300.0%
【
200.0%
】