89
Fig.6-13 Relationship between AI and corresponding setting
Al1 filter time constant is effective when there are sudden changes or noise in the
analog input signal.Responsiveness decreases as the setting increases.
Code
Name
Setting Range
F5.16
AI2 lower limit
0.00
~
10.00V
【
0.00V
】
F5.17
AI2 lower limit corresponding setting
-100.0
~
100.0%
【
0.0%
】
F5.18
AI2 upper limit
0.00
~
10.00V
【
10.00V
】
F5.19
AI2 upper limit corresponding setting
-100.0
~
100.0%
【
100.0%
】
F5.20
AI2 filter time constant
0.00
~
10.00S
【
0.10S
】
Please refer to description of Al1.When AI2 is set as 0-20mA input,the corresponding
voltage range is 0-10V.
Code
Name
Setting Range
F5.21
HDI lower limit
0.00
~
50.00 KHz
【
0.00KHz
】
F5.22
HDI lower limit corresponding setting
-100.0
~
100.0%
【
0.0%
】