60
This parameter is used to set the Max Output frequency of the inverter. It is the basic
of
frequency setting and ACC/DEC speed. Please pay attention to it.
F0.08:
This is the upper limit of the output frequency and it will be less than or equal to the
Max Output frequency.
F0.09:
This is the lower limit of the output frequency of the inverter.
This parameter can be selected by Code F1.12. If the setting frequency is lower
than the upper limit, the inverter will run, stop or hibernate at the lower limit frequency.
The Max. Output frequency
>
Upper limit of the frequency
>
Lower limit of the
frequency.
Code
Name
Setting Range
F0.10
Keypad and terminal UP/DOWN set
0
~
4
【
0
】
The frequency can be set by“
∧
”,“
∨
”and terminal UP/DOWN. This setting method have
the highest and it can be combined with setting channel. It is used to adjust the output
frequency during the commissioning of controlling system.
0:Valid,and the value can be saved when the inverter is powered off. The frequency
command can be set and the value can be saved after the inverter is powered off and it
will combination with the current frequency when it is repower on.
1:Valid,and the value can not be saved when the inverter is powered off. The
frequency command can be set but the value can not be saved after the inverter is
powered off.