112
Fig.6-23 Relationship between bias limit and output frequency
Code
Name
Setting Range
F9.09
PID output upper limit
0.0~100.0%
【
100.0%
】
F9.10
PID output lower limit
-100.0~100.0%
【
0.0%
】
These two parameters are used to restrict the output range of the PID regulator.
Code
Name
Setting Range
F9.11
Feedback lost detecting value
0.0
~
100.0%
【
0.0%
】
F9.12
Feedback lost detecting time
0.0
~
3600.0S
【
2.0S
】
F9.13
Action selections while feedback wire break
0
~
2
【
1
】
Feedback lost detecting value:the values of relative is full scale(100%),The system has
been testing the PID feedback quantity.When the feedback value is less than the
feedback break line readings,the system will start recording time.When the test time is
beyond feedback bolt testing time,the system will alarm feedback lost failure (PIDE).
Code
Name
Setting Range
F9.14
PID initial frequency
0.0~100.0%
【
0.0%
】
F9.15
PID initial frequency keep time
0.0~3600S
【
0S
】