146
0004H
:
In failure
Communicati
on setting
address
2000H
Communication setting range (-
10000~10000) Note: The communication
setting value is the percentage of relative
value (-100.00%~100.00%), which can
be used for communication writing.
When set as a frequency source, the
relative percentage of the maximum
frequency (F0.07); when used as the
torque timing, is the percentage of the
rated motor torque. When given as a PID
or feedback, the corresponding
percentage of the PID.
W
Run/stop
parameter
address
description
3000H Operating frequency
R
3001H Setting frequency
R
3002H Bus voltage
R
3003H Output voltage
R
3004H Output current
R
3005H Speed
R
3006H Output power
R
3007H Output torque
R
3008H PID setting value
R
3009H PID feeback value
R
300AH Terminal input flag status
R