62
Fig.6-1 ACC and DEC time
When the reference frequency is equal to the maximum frequency,The actual
acceleration and deceleration time will be equal to actual setting.
When the reference frequency is less than the maximum frequency,the actual
acceleration and deceleration time will be less than actual setting.
The actual acceleration (deceleration) time=setting ACC/DEC time* reference frequency/
maximum frequency.
Inverter have 4 groups of ACC/DEC time
1st group:F0.11
、
F0.12
;
2nd group:F8.00
、
F8.01
;
3rd group:F8.02
、
F8.03
;
4th group:F8.04
、
F8.05
。
By multifunction digital input terminal of the ACC/DEC time choose terminal
combination to choose ACC/DEC time.
Code
Name
Setting Range
F0.13
Running direction selection
0
~
2
【
0
】
0:Runs at the default direction. the inverter runs in the forward direction.
1:Runs at the opposite direction, the inverter runs in the reverse direction. This effect
equals to the shifting the rotation direction by adjusting either two of the motor wires.
Note: If the parameters are restored,the running direction will be back to its
original status.It is careful to use to system debugging after is forbidden to change
the motor to occasion.