4:Sensor vector control
Refers to the closed-loop vector, must be equipped with encoder and PG card,
suitable for high-precision speed control or torque control.
Code
Name
Setting Range
F0.01
Run command source
0
~
2
【
0
】
Choosing the inverter control instruction.Inverter control command
include:Start,stop,forward,inversion and point movement,fault restoration,etc.
0:Keypad
(“
LOCAL/REMOT”LED extinguished
);
Both RUN and STOP/RST key are used for running command control.If multifunction
key QUICK/JOG is set as FWD/REV switching function
(
F7.03=1
),
it will be used to
change the rotating orientation.In running status,pressing RUN and STOP/RST at the
same time will cause the inverter coast to stop.
1:Terminal
(
“LOCAL/REMOT” LED lights on
);
The operation,including forward run,reverse run,forward jog,reverse jog etc.can be
controlled by multifunctional input terminals.
2:Communication
(
“LOCAL/REMOT”LED flickering
);
The operation of inverter can be controlled by host through communication.
Code
Name
Setting Range
F0.02
Frequency Source A selection
0
~
8
【
8
】
Select frequency A command input channel and there are 8 main given frequency
channels.
0
:
Keypad
Set the frequency by the keypad through modifying F0.06.To achieve the purpose of
the keypad set frequency