InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
360
BTB close/open,
BTB ON coil,
BTB OFF coil,
BTB UV coil,
LCB close/open,
LCB ON coil,
LCB OFF coil,
LCB UV coil
O
THER
B
INARY OUTPUTS
In synchronism,
ReverseSynchro,
ForwardSynchro,
EnginesSwapped
The output terminals that are configured with inversion are closed. Voltage,
current and power measurement is active all the time, regardless of the
actual state of the mains. It is possible to influence breaker under IM-NT
supervision without Wrn MCB fail or Wrn MGCB fail.
After the binary input EMERG. MANUAL is open again, the controller
recovers to the previous mode and behaves according to the actual situation.
Function is active in any controller mode and activation of this input is written
to history.
N
OTE
:
The function is intended especially for Marine gen-sets which are supposed
to be started manually while the controller has no power supply. To recover
successfully from this state, only the signals MCB ON/OFF coil should be
used for mains and breaker control, as the other outputs are continuously
active during Mains operation and it is not possible to switch them between
more control sources.
N
OTE
:
In InteliMains informational outputs SystReady, Syst res OK and other
outputs related to the power management are still active in Emerg. manual
mode even though InteliMains does not play active role in power
management and load sharing. If there are any user defined functions based
on these outputs, blocking those functions (e.g. in PLC) in Emerg. manual
mode should be considered.
C
AUTION
!
Be aware that all outputs related to PLC functions remain functional!
13.2.1.41
Binary input: Alt brightness
Related FW
standard v3.1.0