InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
54
F
UNCTION
N
AME
(
ALPHABETICAL
ORDER
)
B
RIEF
D
ESCRIPTION
R
ELATED
S
ETPOINTS
,
I
NPUTS AND
O
UTPUTS
System Isolated
AA
There are two logical binary inputs that
can be used for secondary CB
feedbacks. When these binary inputs get
activated the corresponding breakers are
considered opened no matter what is the
position of feedbacks of MCB or MGCB.
MCBI
SOLATED
MGCBI
SOLATED
System Load
Control
System Load is a complex function and it
is described in a separate chapter.
SysBaseLoad
SysPwrFactor
SysLdCtrl PtM
SysPFCtrl PtM
Import load
Import PF
MLoad ctrl PtM
PF ctrl PtM
Export limit
TempByPwr Treq
TempByPwr gain
TempByPwr int
MLC:A
N
E
X
S
YS
B
LD
MLC:A
N
E
X
I/E
MLC:TB
Y
P
WR
MPF:A
N
E
X
I/E
System starting
impuls
This is multipurpose starting impulse
which serves as a starting input for gen-
set controllers in the system.
S
YS START
/
STOP
Switchable
Current
measurement
ratio
Using force value function on
MainsCTprim, the controller can
effectively switch the ratio of the current
measurement on the fly (if the
measurement transformers can switch
their amplification).
MainsCTprim
Test on load
and Test on
load with break
InteliMains can perform controlled test on
load in TEST mode. For detailed
description of Test on load please refer
to a separate chapter.
T
EST ON LOAD
Parallel enable
Synchro enable
Island enable
FwRet break
ReturnWithIntr
BreakerOverlap
RetFromIsland
ReturnTo Mains
Time
synchronization
and GPS
positioning with
InternetBridge-
NT
InteliMains obtains data about precise
time and GPS position from
InternetBridge-NT-2.0 (and higher)
connected to the CAN. Time is
broadcasted to all the controllers on CAN
bus. Position is available for monitoring
and for WebSupervisor.
Latitude
Longitude
i