13.2.1.95
Binary input: Force block 1
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have
Protection block
type
configured as
Force block 1
block type are blocked (i.e. temporarily
disabled).
13.2.1.96
Binary input: Force block 2
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have
Protection block
type
configured as
Force block 2
block type are blocked (i.e. temporarily
disabled).
13.2.1.97
Binary input: Force block 3
Related FW
standard v3.1.0
Description
This is one of three binary inputs used for user-defined blocking of
protections. If the input is active, all the protections that have
Protection block
type
configured as
Force block 3
block type are blocked (i.e. temporarily
disabled).
13.2.1.98
Binary input: Lang sel int A
Related FW
standard v3.1.0
Description
This is one of three binary inputs
, used for selecting language of the
built-in
IG-NT terminal (display). As the
IS-NT does not have built-in terminal, this input is assigned to the terminal
(display) #1, which is supposed to be directly attached to the controller or
mounted close to it.
N
OTE
:
Using these inputs for language selection is an option only. If the inputs are
not configured, the language can be selected using the menus on the
terminal.
E
NCODING TABLE
L
ANGUAGE INDEX
I
NPUT
A
I
NPUT
B
I
NPUT
C
0
0
0
0