InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
53
F
UNCTION
N
AME
(
ALPHABETICAL
ORDER
)
B
RIEF
D
ESCRIPTION
R
ELATED
S
ETPOINTS
,
I
NPUTS AND
O
UTPUTS
Remote Control
Function
This particular function enables user to
close or open binary output assigned to
RemoteControl function from
InteliMonitor or via Modbus commands.
For more information please refer to a
separate chapter.
R
EMOTE
C
ONTROL
1
R
EMOTE
C
ONTROL
2
R
EMOTE
C
ONTROL
3
R
EMOTE
C
ONTROL
4
R
EMOTE
C
ONTROL
5
R
EMOTE
C
ONTROL
6
R
EMOTE
C
ONTROL
7
R
EMOTE
C
ONTROL
8
Remote start
and stop of the
system
System controlled by InteliMains can be
started and stopped based on
activation/deactivation of binary input
Rem start/stop. Behavior of the system
then depends on load control mode,
power management, process control and
other factors.
R
EM
S
TART
/S
TOP
RS232 and
RS485
communication
functions
The controller has several settings
regarding RS232 and RS485 functions. It
is possible to set mode of communication
on particular port, speed of
communication and AT commands for
modem connection.
RS232(1) mode
RS232(2) mode
RS232(1)MBCSpd
RS232(2)MBCSpd
RS232(1)MdmIni
RS232(2)MdmIni
RS485(1) conv.
RS485(2) conv.
Soft unloading
and Soft
unloading
based on
Auxiliary
measurement
Soft unloading can be performed in the
standard way or it can be performed
based on actual current to the load or
through MGCB measurement to prevent
sudden overloading of gen-sets because
of other loads on bus. This function is
using Auxiliary current measurement to
ensure that soft unloading is performed
correctly in case of complex installations
(e.g. two Mains incommers).
Soft Unload
AuxCurrCTprim
AuxCurrCTsec
MGCB open lev
MGCB open del
Start Blocked
indication
The controller indicates blocked start of
the gen-set group based on process
limitation setpoints by activation of logical
binary output S
TART
B
LOCKED
(previously
it was indicated by alarm list message).
S
TART
B
LOCKED
StartUpSynchro
nization
AA
StartUpSynchronization is now supported
in InteliMains
NT
controllers.
MultiSoftStart
Synchronization
of separate gen-
sets directly to
the Mains
voltage
This function enables or disables the
direct synchronization of each gen-set to
Mains voltage. This is beneficial for faster
system reaction time after startup.
Moreover, you can use this function to
distribute Mains voltage along bus even if
no gen-set is running.
MGCBparalClose
i