InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
213
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts threshold for mains overvoltage protection.
N
OTE
:
This protection is
Mains protection
type - for more information on protection
types please refer to
alarm types section
.
11.2.6.7
Setpoint: Mains <V MP
Group
Mains protect
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts threshold for mains undervoltage protection.
N
OTE
:
This protection is
Mains protection
type - for more information on protection
types please refer to
alarm types section
.
11.2.6.8
Setpoint: Mains V del
Group
Mains protect
Range [units]
0.00 .. 600.00 [s]
Related FW
standard v3.1.0
Description
The setpoint adjusts the delay for mains under- and overvoltage protections.
The thresholds for these protections are adjusted by setpoints
N
OTE
:
Although the resolution of this setpoint is 0.01s, in fact the adjusted delay is
rounded to the next higher multiple of the period of the mains voltage. The
period is either 0.02s for 50Hz systems or 0.0166s for 60Hz systems. E.g. if
the delay is set to 0.03s at 50Hz system the real delay will be 0.04s.