12.1.7.7
Value: Reserve Stp
Group
Pwr management
Units
kX
Related FW
standard v3.1.0
Description
Actual
absolute reserve
- when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following:
#LoadResStop
plus
Nominal power
of the genset
which is first to stop. #LoadResStop is used from the currently selected
reserve set
.
12.1.7.8
Value: ActRes rel
Group
Power management
Units
%
Related FW
standard v3.1.0
Description
Actual
relative reserve
.
12.1.7.9
Value: ResStart rel
Group
Power management
Units
%
Related FW
standard v3.1.0
Description
If the actual relative reserve is lower than this value the next gen-set which is
about to be started in
power managament
is started. This value is the exact
copy of setpoint
#%LdResStrt X
.
12.1.7.10
Value: ResStp rel
Group
Power management
Units
%
Related FW
standard v3.1.0
Description
Actual
relative reserve
- when the relative reserve is higher than this value
the last started gen-set (the gen-set with the highest priority) is stopped. This
value contains the following: