means MCB stays closed all the time, regardless of
the mains condition.
N
OTE
:
Link the output Sys start/stop with the inputs Sys start/stop at the gen-set
controllers to achieve the automatic start. Gen-set controllers have to be in
AUT mode in order to react on this input.
C
AUTION
!
There are forbidden states for setting BUS VOLTAGE of this setpoint. If MCB
opens on = BUS VOLTAGE it is not possible to set
or MCB CLOSED. This setting is always reverted to NO. If the setpoint
is already set to YES or MCB CLOSED than it is not
possible to set MCB opens on to BUS VOLTAGE (setting is always reverted
to GEN RUNNING).
11.2.8.5
Setpoint: ReturnWithIntr
Group
AMF settings
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
ENABLED
Break transfer of the load back to the mains is enabled. If
reverse synchronizing is not successful, MGCB is opened
and after
DISABLED
Gen-set stays running loaded in island when reverse
synchronizing is not successful, even if mains is OK
again. In this case warning Wrn RSync fail is issued.
N
OTE
:
It is possible to use force values to change this setpoint.