11.2.8 Group: AMF settings
11.2.8.1
Setpoint: EmergStart del
Group
AMF settings
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint sets the delay between the mains failure and the command to
start the gen-set group, i.e. closing the binary output Sys start/stop.
N
OTE
:
Link the output Sys start/stop with the inputs Sys start/stop at the gen-set
controllers to achieve the automatic start. Gen-set controllers have to be in
AUT mode in order to react to this input.
11.2.8.2
Setpoint: FwRet break
Group
AMF settings
Range [units]
0 .. 60.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
MGCB
APPLICATION
This setpoint sets
- the delay between MGCB opening and MCB
closing during the return to mains when reverse
synchronizing (or mains parallel run) is not
enabled.
and
- the delay between MCB opening and MGCB
closing in TEST Mode, when ReturnTo mains =
ENABLED and power cut comes.
MCB
APPLICATION
This setpoint sets the delay between last GCB
opening (from CAN2 bus) and MCB closing during
the return to mains when reverse synchronizing