InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
120
3. The setpoint
Timer settings:
TimerChannel 2
is adjusted to "once" mode, starting date/time
1.5.2010 at 01:00, timer duration 3:00 hrs.
7.16 History Related functions
7.16.1 History Records Adjustment
It is possible to change History records content. Each record contains date, time and cause of the
record as obligatory columns. The rest of columns are configurable.
The history record structure has two parts. The upper part is so-called fast and is written into the
history memory immediately in the moment when the written event occurs. The rest of the record may
be written with a delay max. 100ms. The fast part is intended for fast changing values as e.g. currents,
voltages or power. The parts are separated by a line in the record content list.
1. Values selection tree
2. Buttons for adding/removing values into/from the record structure
3. Buttons for ordering of the values in the record structure
4. Fast history separator. The fast part is located above the separator
5. Estimated number of records depending on record size
6. Record capacity usage indicator