Binary output: ReverseSynchro
Related FW
standard v3.1.0
Description
The output is closed during reverse synchronizing (synchronizing of loaded
gen-set group back to the mains) and opens when the output
activated (= MCB was closed).
N
OTE
:
The output can be used for external synchronizing module control.
14.2.1.69
Binary output: In synchronism
Related FW
standard v3.1.0
Description
This output is closed
during synchronization
when all synchro conditions
have been fulfilled. The output is opened either when:
the synchro conditions are lost
or
the corresponding breaker has been closed
or
the sychronizing was interrupted or timed out.
Synchro conditions are following:
Slip frequency is lower than 0.25 Hz
Phase shift between mains and bus (BusLeft and BusRight - in BTB
application) voltage must be within range of ±
period longer than
Voltage difference between mains and bus (BusLeft and BusRight -
in BTB application) voltage (in all phases) must be lower or equal to
for period longer than
The output is intended for manual synchronization. Automatic closing of
MCB/MGCB
must be disabled
for this case. Use the input
14.2.1.70
Binary output: Ready for Load
Related FW
standard v3.1.0
Description
MGCB application only!
The output closes when the gen-set group is running (Sys start/stop is active)
and output SystReady is active (i.e. sufficient number of gen-sets in Power
management is available).
The MGCB may be already closed or is available to closing.