14.2.1.71
Binary output: ForwardSynchro
Related FW
standard v3.1.0
Description
MGCB application only
The output is closed during forward synchronizing and opens when the
output
is activated (= MGCB was closed).
N
OTE
:
The output can be used for control of an external synchronizing module.
14.2.1.72
Binary output: MGCB status
Related FW
standard v3.1.0
Description
This output indicates the MGCB position, how it is internally considered in the
controller. The position is based on
on the
If only the positive feedback input is used the output mirrors the
feedback.
If both feedbacks are used and they match each other the output
indicates the MGCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other,
the output remains in previous position when they matched.
The output can be used for indication of the MGCB position.
14.2.1.73
Binary output: MCB status
Related FW
standard v3.1.0
Description
This output indicates the MCB position, how it is internally considered in the
controller. The position is based on
If only the positive feedback input is used the output mirrors the
feedback.
If both feedbacks are used and they match each other the output
indicates the MCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other,
the output remains in previous position when they matched.