The reaction time of the thermal overload protection is not fixed; it depends
on how much is the load above the limit (base level). The higher is the load
the shorter the reaction time will be.
E
XAMPLE OF THERMAL OVERLOAD PROTECTION CURVE
N
OTE
:
When the IDMT protection is activated the MCB is opened and the event is
recorded in the Alarmlist and History. The further MCB closing is blocked
until Fault Reset has been pressed to clear the alarm.
11.2.6.4
Setpoint: Mns2Inom prot
Group
Mains protect
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
Enables or disables the mains overcurrent (IDMT) protection. This protection
is evaluated with variable delay. For more information see setpoint