Chapter 3 — Commissioning
Part No. 750-386
3-33
3.18-Secondary Makeup Valve Control
Single Tank
- One secondary makeup valve is
allowed.
Dual Tank
- One secondary makeup valve is
allowed and can be for either the DA or surge
tank.
Secondary makeup valve control has the same
features as the primary makeup valve with the
exception of valve biasing.
The secondary makeup valve tank level set point is typically set
lower than the primary makeup valve tank level set point to allow
the primary makeup valve to modulate first.
A Help Screen is available.
3.19-Steam PRV Valve Control
Steam PRV Control is only available on the DA tank. This feature is
only available if the Overflow Valve option is NOT selected.
The steam PRV uses a PLC analog output for modulating valve
control to maintain tank pressure. A tank pressure transmitter is
required and must be mounted in steam space.
As tank pressure decreases, the PID controlled analog output will
increase to maintain setpoint. As DA tank pressure increases,
control output will decrease, closing the valve.
Manual decrement/increment buttons are only available in Manual
mode.
An operator level password is required to adjust the tank pressure
setpoint.
Output Trend, Tuning and Tank Pressure Trend, and a Help Screen
are available.
Figure 3-32 PRV Control
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...