Chapter 3 — Commissioning
3-42
Part No. 750-386
An operator level password is required to modify any values.
Configurable values are:
Name
Enter any name – 20 characters maximum
Units
Enter any unit – 8 characters maximum
Span
User defined 20ma scaling on analog input device.
Zero entry to 999999 entry limits
Zero
User defined 4ma scaling on analog input device.
-999999 to Span entry limits
Alarm Time Delay
The alarm must be active for this period of time before it is
triggered.
A non-zero value will enable both the high and low alarms.
A value of zero will disable both the high and low alarms.
Flow Input
Yes – will totalize analog input.
Must set time base for totalizer:
0 = sec
1 = min
2 = hr
High Alarm
Low Alarm value to Span value entry limit
Low Alarm
Zero value to High Alarm value entry limit
Figure 3-42 Aux analog input configuration