Chapter 3 — Commissioning
3-32
Part No. 750-386
The DA Primary Makeup Valve (Transfer Valve) may be biased
toward the Full Closed position if the water level in the Surge Tank
becomes too low.
Biasing the transfer valve will help prevent the Surge Tank water
level from reaching a Low Water Cutoff level, disabling the Transfer
Pumps.
Surge Level Bias Set Point 1: This is the Surge Tank level where
biasing begins to be applied to the DA Primary Makeup Valve. Bias
% = 0.
Surge Level Bias Set Point 2: This is the Surge Tank level where the
DA Primary Makeup Valve is being biased at 100%. If the Surge
Tank level reaches Bias Set Point 2 the DA Primary Makeup Valve
will be biased Fully Closed.
During biasing, the DA Primary Makeup Valve control output is still
being influenced by the water level in the DA Tank. The bias is
simply a multiplier to the DA Primary Makeup Valve control output.
The multiplier is linear between 0-100% as Surge Tank level
decreases between Bias Set Point 1 and Bias Set Point 2.
A Help Screen is available.
Figure 3-31 Valve Bias Help
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...