Chapter 3 — Commissioning
Part No. 750-386
3-11
• Requires Communication Watchdog.
Makeup Water Valves
• 2 Valves maximum per tank
• 3 Valves maximum per system
• To provide PID controlled primary and secondary makeup water to
tank(s).
• Reverse acting selection available
Bias DA Primary MUV
• Bias transfer valve (DA Primary MUV) toward close based on Low
Surge Level.
Used to keep transfer pumps from shutting down on low surge tank
water level.
3.9-System Configuration Summary
This screen shows all system configuration settings at a glance.
Upon initial configuration, and any time a critical system
configuration setting (Number of Pumps, System Type, or Pump
Control) is changed, the settings must be confirmed on this screen
in order to continue operation. Press <Confirm Option> to confirm.
When options have been confirmed the <Main> screen button will
be visible.
3.10-Analog Input Configuration
With system configuration completed the Main screen will appear
as follows. Note the <Analog Input Config> button is now visible.
Figure 3-10 System Configuration Summary
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...