Chapter 3 — Commissioning
Part No. 750-386
3-17
3.13.1 - Pump Rotation
Pump rotation is only available on common header applications.
This feature allows for automatic pump Lead Lag order rotation
based on pump rotation elapsed time.
Upon pump rotation:
• Lag 1 pump becomes Lead.
• Lead pump becomes last Lag pump.
Pump rotation time accumulates any time a pump selected as
AUTO is running.
When Pump Rotation Elapsed Time is equal to the Pump Rotation
Time hours the pump will automatically rotate and the Rotation
Elapsed Time will be reset to 0.
Figure 3-18 Pump Configuration (not logged in)