Chapter 3 — Commissioning
Part No. 750-386
3-13
The following should be configured:
Transmitter Span
• Corresponds to 20ma Signal.
• Entry cannot be greater than 99999.
• Entry cannot be less than Zero value.
Transmitter Zero
• Corresponds to 4ma signal.
• Entry cannot be less that -9999.
• Entry cannot be greater than Span value.
High Alarm
• Entry cannot be greater than Span value.
• Entry cannot be less than Low Alarm value.
Low Alarm
• Entry cannot be less than Zero value.
• Entry cannot be greater than High Alarm value.
Alarm Time Delay
• A non-zero entry enables both High and Low Alarm.
• A zero entry disables both High and Low Alarm.
• Enter Time Value 0-9999 Seconds
Figure 3-13 Configure Selected Input (Header Pressure)