Chapter 3 — Commissioning
3-24
Part No. 750-386
3.14.6 - Pump Control - Lead Lag Enabled, NO VFD Selected
Pump Operating Mode
Hand – Off – Auto
Pump Start/Stop
• When Lead Lag is Enabled status indication only. Running -
Stopped
• When Lead Lag is Disabled push button becomes available to
manually start/stop pump.
Pump Status
• Off = Pump not running
• On = Pump running when the VFD option is not selected.
• Fault = Either a pump run fault or pump proving fault is present.
Lead Lag Selection
Press the Pump Lead Lag push buttons to change lead lag order
manually. Lead Lag may only be enabled if the Lead Lag order is
valid.
Lead Lag based on Header Pressure
Pump Proving Status
Only Available if Pump Proving is selected.
Indicates status of Pump Proving switch.