Chapter 3 — Commissioning
3-52
Part No. 750-386
2.Press the Source button to select the storage location of the
application file you want to load.
• Internal Storage - the internal CompactFlash in the
terminal.
• External Storage 1 - the external SD card loaded in the
card slot of the terminal.
• External Storage 2 - USB Flash Drive.
3.Select a .mer file from the list by using the up and down cursor
keys.
4.Press the Load button to load the selected application.You will be
asked if you want to replace the terminal’s communication
configuration with the configuration in the application.
5.Select Yes if this is the first time loading the application;
otherwise select No.
If you select Yes, any changes to the device addresses or driver
properties in the RSLinx Communications screen will be reset to the
CB defaults 192.168.1.150 (PLC) and 192.168.1.152 (HMI).
Notice
The additional functions of the Display Configuration screen should
only be changed by qualified personnel. Improper modification can
render the display inactive.
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...