Chapter 3 — Commissioning
Part No. 750-386
3-23
3.14.5 - Pump Control - Lead Lag Enabled (Transfer Pump, Dual
Tank systems), VFD Selected
Pump Operating Mode
Hand – Off – Auto - VFD Bypass
Pump Start/Stop
• When Lead Lag is Enabled status indication only. Running -
Stopped
• When Lead Lag is Disabled push button becomes available to
manually start/stop pump.
Pump Status
• Off = Pump not running
• On = Pump running in Hand mode.
• Pump Speed% = Pump running in Auto; % is the commanded
output to the VFD.
• Fault = Either a pump run fault or pump proving fault is present.
• VFD Bypass = VFD is in bypass mode.
Lead Lag Selection
Press the Pump Lead Lag push buttons to select or change the lead
lag order manually. Pump Lead Lag may only be enabled if the lead
lag order is valid. Lag pumps stage on and off based on the VFD
output%.
Pump Proving Status
Only Available if Pump Proving is selected.
Indicates status of Pump Proving switch.
Transfer Pump Runtime Hours
Service level password required to reset run time hours and rotation
elapsed time.
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...