Chapter 3 — Commissioning
3-18
Part No. 750-386
3.13.2 - Pump Auto Restart
This feature allows for Automatic Pump Restart after an Analog Low
Water Cutoff Alarm.
• Requires tank level transmitter.
• Pump Lead Lag must be enabled to auto restart pumps.
• Pump Restart Level entry must be less than the tank level
transmitter span value.
• Pump Restart level entry must be greater than the tank level low
alarm value.
After an Analog Low Water Cutoff the pumps will automatically
restart when the Tank Level rises above the Pump Auto Restart
Level. If desired, the LWCO alarm may be acknowledged from the
HMI; as long as tank level is above LWCO level the pump will restart
even if tank water level is still below the auto restart level. Should
an analog LWCO alarm occur with Pump Auto Restart disabled,
Pump Lead Lag will be automatically disabled with manual
intervention required to restart the pumps.
In most cases the analog LWCO level should be set above the
discrete LWCO switch.
Should the discrete Low Water Cutoff Switch be tripped, Pump Lead
Lag remains enabled but alarm acknowledgment is required to
restart the pumps.
Figure 3-19 Pump Configuration (after login)
Summary of Contents for ADAC 1000
Page 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Page 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Page 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Page 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Page 120: ...A 26 Part No 750 386...
Page 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Page 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Page 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Page 139: ......
Page 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...